Channel Veritas2 Fire Detection Systems
The range of Veritas2 Fire Detection Systems from Channel offer both a 2 or a 4 zone panel that is realistically priced system and that does not compromise on quality in any way.
All of the panels in this range are EN54-2 control interfaces complete with EN54-4 power supply systems.
In addition, the comprehensive Veritas2 range offers a collection of accessories expertly designed to ensure a professional and reliable system combining modern stylish appearance with a high level of functionality making them a ideal solution for even the most challanging installation assuring total peace of mind to both the installer and the end user.
Features and Benefits
|
Technical Specification
| POWER | |
| Mains Supply | 230V AC minus 15 per cent, plus 10 per cent, 50Hz |
| Standby Supply | 2 x 12V batteries 2.1Ah |
| Minimum Current | 24mA |
| Maximum Current | 1.2A |
| Mains Protection | 1A time-lag fuse |
| ZONES (2 or 4) | |
| Maximum Detectors per Zone | 32 |
| Zone Voltage | 21V plus 1 to 2 per cent |
| End of Line Unit | 24V TVS diode (P6KE24CA) |
| Zone Alarm Current | Limited to 100mA |
| Zone Fault Current | Limited to 18mA |
| Maximum Zone Wiring | 1000 metres (1.5mm)/120 ohms |
| RELAYS, INPUTS AND OUTPUTS | |
| Fire Relay | Change over contacts rated at 24V 3A |
| Fault Relay | Normally closed relay rated at 24V 3A |
| Programmable Relay | Change over contacts rated at 24V 3A |
| Auxiliary 24V DC Supply | Maximum 100mA at 24V |
| Repeater Panel | Maximum 4 repeaters (1000m total wiring) |
| Programmable Input | Required normally open input to select |
| Sounder Circuits | 2 circuits each rated at 24V 500mA |
| ENVIRONMENT | |
| Dimensions | (w)370mm x (h) 295mm x (d) 90mm |
| Weight | 2.8kgs approx |
| Warranty | 5 years |